Damper Don's Website

About Dampers : TYPICAL APPLICATIONS FOR GUILLOTINES

Typical Applications For Guillotines

Example – Coal Fired Electricity Generation Station

  • Precipitator Inlet and Outlet Isolation.

  • SOx Scrubber Inlet and Outlet Isolation

  • Scrubber Bypass Isolation

  • Stack Isolation

  • Hot Gas Fan Isolation

Typical Installation:


There are usually lots more dampers than shown above because a large boiler requires a number of precipitators and scrubber modules. Parallel systems are used so the main power generation system is not shut down for maintenance on a back end system. This is demonstrated in the following sketch.

Location Of Isolation Dampers In A Typical Flue Gas Clean-Up System

Legend

 

P – Electrostatic Precipitators

F – Induced Draft Fan (Booster Thru Scrubber)

S – SOx Wet Scrubber Towers

ST – Chimney Of Stack

1 – Precipitator Inlet Isolation Damper

2 – Precipitator Outlet Isolation Damper

3 – ID Fan Outlet Damper

4 – Scrubber Inlet Isolation Damper

5 – Scrubber Outlet Isolation Damper

6 – Bypass Isolation Damper

7 – Stack Isolation Damper

These dampers are usually designed to have a 100% shut-off capability because when they are closed, men will be working behind them. Remember hot corrosive flue gas in small amounts "kills".

The dampers shown above could easily represent $2-5 million, depending on their physical size and materials of construction.